product data sheet 3rv2011-1ja10 circuit-breaker sz s00, for motor protection, class 10, a-release 7...10a, n-release 130a, screw connection, standard sw. capacity general technical data: product brand name sirius product designation 3rv2 circuit breaker size of the circuit-breaker s00 trip class class 10 protection class ip / on the front ip20 degree of pollution 3 installation altitude / at a height over sea level / maximum m 2,000 ambient temperature ? during storage c -50 ? +80 ? during operating c -20 ? +60 ? during transport c -50 ? +80 resistance against shock 25g / 11 ms impulse voltage resistance / rated value kv 6 insulation voltage / rated value v 690 active power loss / total / typical w 8.7 item designation ? according to din 40719 extendable after iec 204-2 / according to iec 750 f ? according to din en 61346-2 f 3rv2011-1ja10 page 1/ 09/14/2012 subject to modifications ? copyright siemens ag 2012 6
mechanical operating cycles as operating time ? of the main contacts / typical 100,000 ? of the auxiliary contacts / typical 100,000 type of the driving mechanism / motor drive no design of the operating mechanism selector switch product function ? overload protection yes ? phase disturbance recognition yes product component ? auxiliary switch no ? undervoltage release mechanism no ? trip indicator no product extension / optional / motor drive no main circuit: number of poles / for main current circuit 3 operating voltage / at ac-3 / rated value / maximum v 690 operating current / at ac-3 / at 400 v / rated value a 10 service power / at ac-3 ? at 400 v / rated value w 4,000 ? at 500 v / rated value w 5,500 ? at 690 v / rated value w 7,500 frequency of operation / at ac-3 / according to iec 60947-6-2 / maximum 1/h 15 arrangement of electrical connectors / for main current circuit top and bottom adjustable response current ? of the non-delayed short-circuit release a 130 ? 130 ? of the current-dependent overload release a 7 ? 10 service power / at ac-3 / at 230 v / rated value w 2,200 continuous current / rated value a 10 auxiliary circuit: product extension / auxiliary switch yes number of nc contacts / for auxiliary contacts / instantaneous switching 0 number of no contacts / for auxiliary contacts / instantaneous switching 0 number of change-over switches / for auxiliary contacts 0 inputs/ outputs: number of digital inputs 0 3rv2011-1ja10 page 2/ 09/14/2012 subject to modifications ? copyright siemens ag 2012 6
short-circuit: breaking capacity limit short-circuit current (lcu) ? at 400 v / rated value a 100,000 ? at 500 v / rated value a 42,000 ? at 690 v / rated value a 6,000 design of the overcurrent release and short-circuit release thermomagnetic installation/mounting/dimensions: mounting position any type of mounting screw and snap-on mounting onto 35 mm standard mounting rail according to din en 60715 width mm 45 height mm 97 depth mm 91 distance, to be maintained, to the ranks assembly ? forwards mm 0 ? backwards mm 0 ? upwards mm 50 ? downwards mm 50 ? sidewards mm 0 distance, to be maintained, to earthed part ? forwards mm 0 ? backwards mm 0 ? upwards mm 50 ? sidewards mm 30 ? downwards mm 50 distance, to be maintained, conductive elements ? forwards mm 0 ? backwards mm 0 ? upwards mm 50 ? downwards mm 50 ? sidewards mm 30 connections: product function ? removable terminal for main circuit no ? removable terminal for auxiliary and control circuit no design of the electrical connection ? for main current circuit screw-type terminals type of the connectable conductor cross-section ? for main contacts 3rv2011-1ja10 page 3/ 09/14/2012 subject to modifications ? copyright siemens ag 2012 6
? solid 2x (0.75 ... 2.5 mm2), 2x 4 mm2 ? finely stranded ? with conductor end processing 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2) ? for awg conductors / for main contacts 2x (18 ... 14), 2x 12 certificates/approvals: verification of suitability ce / ul / csa / ccc ? fr staubexplosionsschutz fr zone 21/22 no ? for gas explosion protection for zone 1/2 no general product approval for use in hazardous locations declaration of conformity test certificates other special test certificate type test certificates/test report shipping approval other other ul/csa ratings yielded mechanical performance (hp) ? for single-phase squirrel cage motors ? at 110/120 v / rated value hp 0.5 ? at 230 v / rated value hp 1.5 ? for three-phase squirrel cage motors ? at 200/208 v / rated value hp 2 ? at 220/230 v / rated value hp 3 ? at 460/480 v / rated value hp 5 ? at 575/600 v / rated value hp 7.5 operating current (fla) / for three-phase squirrel cage motors ? at 480 v / rated value a 7.6 ? at 600 v / rated value a 9 safety: 3rv2011-1ja10 page 4/ 09/14/2012 subject to modifications ? copyright siemens ag 2012 6
b10 value / with high demand rate ? according to sn 31920 50,000 t1 value / for proof test interval or service life ? according to iec 61508 a 10 failure rate (fit value) / with low demand rate ? according to sn 31920 fit 50 proportion of dangerous failures ? with low demand rate / according to sn 31920 % 40 ? with high demand rate / according to sn 31920 % 40 protection against electrical shock finger-safe further information: information- and downloadcenter (catalogs, brochures,?) http://www.siemens.com/industrial-controls/catalogs industry mall (online ordering system) http://www.siemens.com/industrial-controls/mall cax-online-generator http://www.siemens.com/cax service&support (manuals, certificates, characteristics, faqs,...) http://support.automation.siemens.com/ww/view/en/3rv2011-1ja10/all image database (product images, 2d dimension drawings, 3d models, device circuit diagrams, ...) http://www.automation.siemens.com/bilddb/cax_en.aspx?mlfb=3rv2011-1ja10 3rv2011-1ja10 page 5/ 09/14/2012 subject to modifications ? copyright siemens ag 2012 6
last change: sep 12, 2012 3rv2011-1ja10 page 6/ 09/14/2012 subject to modifications ? copyright siemens ag 2012 6
|